run_uk_sweep#
- popo.powerflow.run_uk_sweep(build_circuit, customers_of, monitor, kv, horizon, pv_profile, ev_profiles, ev_levels=(0.0, 0.2, 0.4, 0.6), pv_levels=(0.0, 0.2, 0.4, 0.6), volt_var=None, sizing=None, mv_voltage=None, weather_path=None, start='2019-01-01', seed=0, start_step=0, customer_voltages=False)#
Sweep EV x PV penetration on one UK-style feeder with one substation.
This is the DSS-UK case study: a stiff or weak secondary substation selected by voltage sensitivity, with independent customer power-factor profiles and a Q(U) droop on PV inverters decoupling P from Q, and the MV source voltage following a demand-dependent profile within a tap-changer deadband.
monitoris one transformer rather than a population, and the result frame carries the feeder-head quantitiessolve_time_series()already records for every monitored transformer.- Parameters:
build_circuit (
Callable[[],Any]) – Returns an already-compiled circuit, with base household loads attached, fresh for each scenario. Installing an MV-voltage loadshape ontoVsource.Sourcebefore returning is the caller’s job ifmv_voltageis not given here.customers_of (
Callable[[Any],Sequence[tuple[str,str]]]) – Eligible(load name, bus)pairs for DER installation, given the compiled circuit.monitor (
Transformer) – The transformer to record.kv (
float) – Service voltage of a customer connection.horizon (
int) – Number of steps to solve per scenario.pv_profile (
ndarray) – Per-unit generation profile, shared across the sweep.ev_profiles (
ndarray) – Charging power, shape(intervals, vehicles).volt_var (
VoltVarCurve|None) – Reactive characteristic installed with any PV;Noneleaves inverters at unity power factor.sizing (
ArraySizing|None) – Rooftop array size distribution; defaults to a domestic one.mv_voltage (
MVVoltageProfile|None) – If given, built once per scenario and written onto the circuit’s source as adaily/yearlyloadshape before DER is attached, reproducing the original runner’s varying MV busbar.weather_path (
Path|None) – If given, the sweep’s output is joined with irradiance and temperature from this path viapopo.network.weather.attach_weather().start (
str) – First timestamp of the horizon, stamped onto every scenario.seed (
int) – Seed for customer and DER-size draws, fixed across the sweep so the same customers hold the technology at every level.start_step (
int) – Step offset at which every scenario begins solving.customer_voltages (
bool) – Also recordv_cust_min_pu,v_cust_p05_puandv_cust_max_puover each monitored transformer’s own customers, found bypopo.network.transformer_customers(). Compliance with a voltage standard is judged there, not at the busbar.
- Return type:
- Returns:
A