PVDerating#

class popo.scenarios.PVDerating(temperature_coefficient=-0.004, noct_c=45.0, dc_losses=0.14, eta_nominal=0.96)#

Bases: object

Temperature, DC-loss and inverter-efficiency derating for irradiance-driven PV.

Used when the generation profile is plane-of-array irradiance (kW/m2) rather than an AC output per kWp that already includes these losses, such as a PV-Watts series. The chain follows PV-Watts v5, expressed through OpenDSS’s own PVSystem mechanism (P-TCurve, EffCurve, Tyearly):

  • cell temperature from the NOCT model, T_cell = T_amb + (NOCT - 20) / 0.8 * G with G in kW/m2 (OpenDSS applies P-TCurve to panel temperature);

  • array power falling by temperature_coefficient per kelvin above 25 degC (standard test conditions), about -0.4 %/K for crystalline silicon;

  • dc_losses (soiling, wiring, mismatch, ageing), 14 % in PV-Watts;

  • inverter efficiency against DC load z per unit of rating, from PV-Watts v5: eta = (eta_nominal / 0.9637) * (-0.0162 z - 0.0059 / z + 0.9858).

Variables:
  • temperature_coefficient – Relative power change per kelvin of cell temperature.

  • noct_c – Nominal operating cell temperature, degC.

  • dc_losses – Fraction of DC power lost before the inverter.

  • eta_nominal – Inverter efficiency at rated load.

cell_temperature(ambient_c, irradiance_kw_m2)#

Cell temperature from ambient temperature and plane-of-array irradiance (NOCT model).

Return type:

ndarray

power_temperature_curve()#

P-TCurve points: per-unit Pmpp against cell temperature, -20 to 100 degC.

Return type:

tuple[list[float], list[float]]

efficiency_curve()#

EffCurve points: inverter efficiency against per-unit DC load (PV-Watts v5).

Return type:

tuple[list[float], list[float]]