bus_voltages#
- popo.powerflow.bus_voltages(dss)#
Per-phase voltage magnitude and angle at every bus.
The phase is the node the bus is actually connected on, not its position among the bus’s nodes: a single-phase service on phase 2 is labelled phase 2.
Bus.puVmagAnglereturns one pair per connected node in node order, so numbering the pairs 1, 2, 3 would label that service phase 1, and a phase identification or balancing study reading it would be wrong without any error to show for it.